Some radiators hot, others barely warm? How to balance your radiators (UK)

If the radiators nearest the boiler are hot and the far ones barely warm, the system needs balancing. How to find the order they warm up, measure the drop across each radiator, close each lockshield right down and open it a quarter turn, and do it without a thermometer, with a balancing log that says which valve to turn next.

2:50 videoWritten steps below

If the radiators nearest the boiler get hot and the ones further away stay lukewarm, the heating probably needs balancing. Hot water takes the easiest route round the pipes, and the radiators on the shortest runs have the least resistance, so they take more than their share. Balancing means setting a small valve on each radiator, the lockshield, so every radiator gets enough. You can do it yourself with a spanner, ideally two clip-on pipe thermometers, and a couple of hours. Viessmann points out that valves can weep when you turn them, so keep a cloth handy, and if one keeps dripping, stop and call a heating engineer.

Balancing won’t fix a radiator that’s cold at the top (that’s air), cold at the bottom (usually sludge), or one that stays cold once the others are balanced (often a stuck valve pin). Our cold radiator guide covers those.

What you’ll need

  • A lockshield valve key or an adjustable spanner

    To turn the small square spindle under the lockshield cap. Vaillant and Viessmann list either.

    Lockshield valve keys on Amazon
  • Two clip-on pipe thermometers

    One for the pipe in, one for the pipe out. Drayton recommends two contact thermometers.

    Pipe clamp thermometers on Amazon
  • Electrical tape, if you use an infrared thermometer

    Infrared thermometers read low on shiny copper. Fluke suggests a piece of electrical tape on the surface; aim at the tape.

  • A radiator key

    For bleeding any radiator that’s cold at the top before you start.

    Brass radiator keys on Amazon
  • A pencil and paper

    For the order the radiators warm up, the readings and the turns on each lockshield.

Amazon links are affiliate links. If you buy through one, HanaHow gets a small commission and you pay the same. As an Amazon Associate I earn from qualifying purchases.

The two valves

Each radiator has a valve at each end.

  • The one you turn by hand. On most radiators this is a thermostatic radiator valve, with a numbered head. On older radiators it may be a plain wheel-head valve.
  • The lockshield. At the other end, under a plastic cap you can pull or unscrew off. Underneath is a small square spindle that turns with a lockshield key or an adjustable spanner. It sets how much water goes through this radiator, and once it’s set you leave it alone.

A radiator with a lockshield at both ends and no hand valve may be there on purpose, to keep water moving through the boiler when everything else shuts; Ideal’s manual says those stay open, so leave them alone.

Clockwise closes the lockshield, anticlockwise opens it, looking down at the spindle. Drayton, Honeywell, Vaillant and Viessmann all say so. The pipe going in can be at either end, so measure both pipes rather than assuming.

Before you start

  1. Start cold. Vaillant says to watch the system heat up from a completely cold start, and Viessmann says to let the radiators cool down completely first. First thing in the morning, before the heating comes on, works well.
  2. Bleed any radiator that’s cold at the top, with an old towel under the bleed valve, then check the boiler pressure. Our cold radiator guide shows both, and the boiler pressure guide covers a boiler that keeps losing it.
  3. Turn every thermostatic valve to maximum, or take the heads off. Ideal, Drayton and Heat Geek all have them fully open while you balance, so none of them closes partway through and throws the readings out. Wheel-head valves go fully open too.
  4. Open every lockshield fully. Turn each spindle anticlockwise until it stops. Drayton’s commissioning instructions start with every valve fully open.
  5. With a hot water cylinder, switch the hot water off on the programmer while you balance. Drayton’s instructions start with the cylinder’s circuit closed, so it isn’t taking hot water away from the radiators. With a combi, don’t run a hot tap while you measure: the boiler switches over to the tap and the radiators cool.

Find the order

Put the heating on, with the room thermostat turned right up so it doesn’t switch off part way, and walk round the house, noting the order the radiators warm up. Vaillant says to record the order they reach full temperature. It’s usually nearest the boiler first, but “nearest” means nearest along the pipes, which you can’t see, so a radiator in the room above the boiler can come later than one downstairs. A helper on the other floor makes this easier.

Measure the drop

On each radiator, measure the pipe going in and the pipe coming out, a few centimetres from each valve, once it’s fully warm. The difference between them is the drop.

What heats the water Drop to aim for Who says so
A condensing gas or oil boiler About 20°C Ideal’s installation manual (the Irish edition of the Logic Max Combi2): “around 20 °C temperature drop at each radiator”. Potterton (Baxi) recommends a 20°C drop for condensing boilers, and Worcester Bosch sizes radiators for them at 70°C in and 50°C out.
An older, non-condensing boiler About 11°C Older systems were designed round 10 to 11°C: Worcester Bosch sizes radiators for a standard-efficiency boiler at 80°C in and 70°C out, and Drayton’s TRV commissioning instructions, written for those systems, say “usually 11C”.
A heat pump About 5 to 7°C Heat Geek. That’s too close to feel by hand, so it’s usually a job for the installer.

A boiler with a white or grey plastic condensate pipe running to a drain is a condensing boiler.

Don’t chase the exact number. Heat Geek calls trying for a perfect 20°C at every radiator “unnecessary and difficult”, and the log below counts anything within about a fifth of the target as close enough, which is our rule of thumb rather than anyone’s spec. On an older system where the radiators are only just big enough, Baxi’s Potterton manual suggests keeping to 11°C even with a condensing boiler.

Clip-on pipe thermometers are easiest. Drayton recommends two contact thermometers. An infrared thermometer or thermal camera works too, but they read low on shiny copper: Fluke, which makes them, says low emissivity makes them under-report, and suggests a piece of electrical tape on the surface. Put a strip on each pipe and aim at the tape.

Adjust one radiator at a time

  1. Start with the radiator that warmed up first.
  2. Measure both pipes. If the drop is too small, too much water is going straight through.
  3. Close its lockshield right down, clockwise, counting the turns, then open it a quarter turn. Heat Geek says it’s typically only the last three quarters of a turn before closed that has any effect on flow, so from fully open, small turns do nothing.
  4. Wait until the readings stop changing, then measure again. Drayton says to wait for the readings to stabilise; there’s no fixed time.
  5. If the drop is still too small, close it a little more. If it’s now too big, open it a little. Repeat until it’s close to the target.
  6. Move to the next radiator in the order and do the same.
  7. Leave the last radiator fully open. Heat Geek says you should always have at least one valve completely open.

Each change pushes more water on to the radiators after it, so a far radiator that was too cool often comes good once the ones before it are set. Expect to go round more than once.

The balancing log below keeps track: put your radiators in order, type the two temperatures for each, and it says which lockshield to turn next.

Balancing log

List your radiators in the order they warm up, first to last. Type the two pipe temperatures for each, and it says which lockshield to turn next.

Your heating
What heats the water?

Aim for a drop of about 20°C between the pipe in and the pipe out. Ideal’s installation manual: around 20°C at each radiator.

Your radiators, in the order they warm up
  1. 19°C drop On target

  2. 11°C drop Close a little

  3. 14°C drop Close a little

  4. 28°C drop Waiting

Next: Bathroom. Close it right down, then open a quarter turn.

The drop is too small: water’s rushing straight through. Close the lockshield right down, clockwise, counting the turns, then open it a quarter turn. Untick Fully open and put ¼ in Turns open. Wait for the readings to settle, then measure again.

The log stays on this page and isn’t saved. Write your readings and turns down as you go. It counts a radiator as on target within about a fifth of the target either way. That’s our rule of thumb: Heat Geek calls hitting a perfect 20°C at every radiator “unnecessary and difficult”.

Without a thermometer

Vaillant, the boiler maker, gives a rough version:

  1. In the order the radiators warmed up, close each lockshield fully, clockwise.
  2. Open each one roughly a quarter turn, anticlockwise, and the radiators further away a small amount more than the earlier ones. Viessmann’s version says to open it slightly, and that the furthest may need opening more.
  3. Leave the last radiator fully open. Heat Geek says you should always have at least one valve completely open.
  4. Vaillant’s check is to run the heating again from a cold start and watch the radiators warm up, until they heat up close together.
  5. To check one by hand, touch the pipe in and the pipe out briefly, with the same hand so the comparison is fair. If they feel equally hot, water’s still rushing through, so close that lockshield a touch more. Heat Geek says many systems may be close enough “by simply feeling the return pipe with your hand”.

Then live with it for a day or two and adjust any room that’s still too cold or too warm.

When you’ve finished

  • Write down the turns for each radiator. If you take a radiator off to decorate, you can close the lockshield, counting the turns, and open it the same number afterwards.
  • Put the thermostatic heads back and set them to the temperature you want, then set the room thermostat and programmer back to normal, and switch the hot water back on if you turned it off. Drayton says to allow two hours for the rooms to settle.
  • Leave pump speed and bypass settings to a heating engineer.

If a radiator still won’t heat

If one radiator still stays cold with its lockshield fully open once the others are balanced, or it’s cold in patches, balancing won’t fix it. Check for air (cold at the top), sludge (cold at the bottom) or a stuck thermostatic valve pin (cold all over), all in our cold radiator guide. If nothing gets hot at all, or a combi gives hot water but no heating, call a Gas Safe registered engineer.

Combi, system and regular boilers

The method is the same for a combi and for a system or regular boiler with a hot water cylinder. A cylinder’s heating coil takes water from the same pipes, and Drayton’s instructions balance it too, to an 11°C drop. That’s usually a job for a heating engineer.

Does balancing save money?

Viessmann and Which? both say a badly balanced system can cost more to run, but nobody we found gives a reliable figure for what balancing saves. Heat Geek argues it doesn’t make a modern boiler condense more. What it does do is warm the rooms evenly, so you’re less likely to turn the thermostat up to heat the cold ones.

Once it’s balanced, you may be able to turn the boiler’s flow temperature down. The Energy Saving Trust suggests it, saying research from Nesta shows that 60°C improves a boiler’s efficiency by nearly 4%. With a hot water cylinder, it says not to set it lower than 65°C, or the boiler won’t be able to heat the cylinder to a safe temperature.